Thus we connect — read only
The value comes fromModbus TCP · Plant PLC · M-Bus (meters)of the installation —read, not controlled. Everything isin the housecalculated, nothing leaves the house. No obligation to disclose operational data.
Your own LLM for CHP — offline
Questions in plain language, answered byYour own installation data— local, no cloud. The AI runs internally; the installation remains yours.
Regulatory framework:NF ISO 8528 (generator sets) (CHP Test) · Manufacturer specifications (Maintenance plan)
Associated causal chains
This component is part ofInstallation causal chains— from cause to effect (gas quality → engine → exhaust gas → heat → efficiency). The AI reads the entire chain, not just the individual value.
Link with the entire installation
A CHP unit is never alone: electricity, heat and gas are linked, and with PV and battery storage, it becomes a system. The AI calculates the entire installation.
Frequently asked questions
How often must the oil in the gas engine be changed?
The standard replacement cycle for gas engines in CHP units is 2,000 operating hours using specific oil for gas engines.
What oil temperature is normal for the CHP?
The operating temperature of the lubricating oil must be between 75 and 90 °C.
From what point does oil consumption indicate wear?
An oil consumption higher than 0.8 g/kWh indicates increased mechanical wear.
What oil pressure is correct for the gas engine?
The service pressure of the lubricating oil must be constant between 3.5 and 5.0 bar.
Why is the cooling water temperature important?
The cooling water temperature (reference value approx. 83.4 °C) serves to monitor the thermal load and the efficiency of the heat exchanger.
What are the effects of incorrect oil on the CHP?
Inappropriate oil leads to faster oxidation, foam formation and therefore reduced lubrication of the bearings.